WATERLINK - TXVA 24kV

Products

TXVA 24kV 3x50mm² 2xR5,0 Zn

Nexans ref. 10565298

  • Packaging: Cut to length (m)
  • Nominal outer diameter: 80.4 mm
  • Conductor cross-section: 50 mm²
  • Conductor diameter: 8.2 mm
  • Diameter over insulation: 23.9 mm
  • Permissible current rating in open air: 225 A
  • Permissible current rating when buried: 215 A

TXVA 24kV 3x95 mm² + GS48 2xR5,0 Zn

Nexans ref. 10564342

  • Packaging: Cut to length (m)
  • Nominal outer diameter: 83.6 mm
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.5 mm
  • Diameter over insulation: 25.8 mm
  • Permissible current rating in open air: 330 A
  • Permissible current rating when buried: 310 A

TXVA 24kV 3x240 mm² + 2xGS48 2xR3,2 Zn

Nexans ref. 10564309

  • Packaging: Cut to length (m)
  • Nominal outer diameter: 96.3 mm
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.35 mm
  • Diameter over insulation: 34.5 mm
  • Permissible current rating in open air: 570 A
  • Permissible current rating when buried: 515 A

TXVA 24kV 3x240 mm² + GS96 2xR3,2 Zn

Nexans ref. 10564144

  • Packaging: Cut to length (m)
  • Nominal outer diameter: 96.3 mm
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.35 mm
  • Diameter over insulation: 34.5 mm
  • Permissible current rating in open air: 570 A
  • Permissible current rating when buried: 515 A

TXVA 24kV 3x240mm² 2xR3,2 Zn

Nexans ref. 10564142

  • Packaging: Cut to length (m)
  • Nominal outer diameter: 96.3 mm
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.35 mm
  • Diameter over insulation: 34.5 mm
  • Permissible current rating in open air: 570 A
  • Permissible current rating when buried: 515 A

Description

Description

Standards

  • International
    IEC 60228; IEC 60502-2; Nexans specification

Armored PEX insulated submarine cables for utilities.

 

Construction:
 

Conductor:
Round multiple wire, compressed copper conductor

Conductor screen:
Extruded layer of semi-conductive cross-linked polyethylene.

Insulation:
Extruded insulation of cross-linked polyethylene.

Insulation screen:

Extruded insulation of cross-linked polyethylene.

Twisting and bonding:
Three insulated conductors are twisted together and bonded with semiconducting bands.
Fillers are installed in the winding rooms.
If desired, fiber cables can also be inserted into the winding rooms.

Armouring:
2 layers of galvanized steel wires.
Zinc wires can be inserted into the reinforcement if desired.

Outer corrosion protection:
Two layers of polypropylene yarn with bitumen.

 

The dimensions and weights given are based on IEC 60502. In other cases, the values ​​given will vary.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Number of cores
3

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close