LiHCH 4x0,75 mm² 300/500V
LiHCH 4x0,75 mm² 300/500V
Flexible shielded signalcable
Read more- Nexans ref. : 10567432
- Country ref. : 1005619
- EAN : 7045210081015
Description
Description
Standards
-
ProductIEC 60228
-
TestIEC 60332-1-2; IEC 60754-2; IEC 61034-2
LiHCH 300/500 V is a flexible halogenfree shielded signal cable that is widely used in control systems. LiHCH 300/500 V is a natural choice for signaling-, Instrumentation-, process and facility systems. The cable is primarily designed for indoor use, but can be used outdoors with extra protection. The conductors are color-coded according to DIN 47100. LiHCH 300/500 V can be supplied as a PVC cabel, it is then called LiYCY.
Technical Data
- Operating Voltage:
0.22 mm² - 0.34 mm² 250 V
≥0.50 mm2 300/500 V
- Test Voltage:
0.22 mm² - 0.34 mm² 1200 V
≥0.50 mm2 2000 V
- Insulation Res.: > 200 MOhm km
- Temperature Range: -20°C … + 70°C
- Temperature Range Flexible -5°C … + 70°C
- Min. Bending Radius: 10 x Overall Diameter
Construction
- Class 5 annealed copper conductors according to IEC 60228
- HFFR insulation, with colour coding according to DIN47100
- Polyester tape wrapping
- Tinned copper wire braiding
- HFFR outer sheath, RAL7001 Grey Colour
- Reference Standards: VDE 0814 and VDE0812
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Tinned copper braid
Conductor flexibility
Flexible class 5
Conductor material
Bare copper class 5
Insulation
HFFR
Outer sheath
HFFR (Halogen Free Flame Retardant)
Overall screen
Aluminium/polyester tape
Sheath colour
Grey RAL 7001
Type of conductor
Stranded, round, class 2
With Green/Yellow core
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
71 kg/km
Outer Diameter
6.5 mm
Conductor cross-section
0.75 mm²
Conductor diameter
- mm
Nominal outer diameter
- mm
Number of cores
4
Electrical characteristics
Electrical characteristics
Breakdown voltage
- kV
Operating voltage
- V
Rated Voltage Uo/U (Um)
0.3/0.5(0.6)kV
Resistance of the insulation
200 MOhm
Test voltage
2000 V
Usage characteristics
Usage characteristics
Minimum bending radius, static (XD)
10
Operating temperature flexing, range
- °C
Operating temperature, fixed, range
-20 ... 70 °C
RoHS compliant
Yes
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000956-NOLA
- Certification Date : 10/14/20
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 1783
- Declared performance : Dca-s2,d2,a2