TSLF 24 - 36kV three core

Products

TSLF 24kV 3x1x50A

Nexans ref. 10166755 - Country ref. 1067125

  • Packaging: Drum (500m)
  • Conductor cross-section: 50 mm²
  • Nominal outer diameter: 58.2 mm
  • Approximate weight: 2.062 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 185 A
  • Perm. current rating in air 25°C - trefoil formation: 195 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 4.5 kN

 

TSLF 24kV 3x1x95A

Nexans ref. 10166756 - Country ref. 1067126

  • Packaging: Drum (500m)
  • Conductor cross-section: 95 mm²
  • Nominal outer diameter: 65.9 mm
  • Approximate weight: 2.873 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 280 A
  • Perm. current rating in air 25°C - trefoil formation: 280 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 8.55 kN

 

TSLF 24kV 3x1x150A

Nexans ref. 10166757 - Country ref. 1067127

  • Packaging: Drum (500m)
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 72.6 mm
  • Approximate weight: 3.588 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 360 A
  • Perm. current rating in air 25°C - trefoil formation: 370 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 13.5 kN

 

TSLF 24kV 3x1x240A

Nexans ref. 10166758 - Country ref. 1067128

  • Packaging: Drum (500m)
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 82.1 mm
  • Approximate weight: 4.945 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 465 A
  • Perm. current rating in air 25°C - trefoil formation: 490 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 21.6 kN

 

TSLF 24kV 3x1x400A

Nexans ref. 10265297 - Country ref. 10265297

  • Packaging: Drum (500m)
  • Conductor cross-section: 400 mm²
  • Nominal outer diameter: 95.5 mm
  • Approximate weight: 6.723 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 615 A
  • Perm. current rating in air 25°C - trefoil formation: 680 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 36 kN

 

TSLF 24kV 3x1x630A

Nexans ref. 10558139 - Country ref. 1067137

  • Packaging: Drum (500m)
  • Conductor cross-section: 630 mm²
  • Nominal outer diameter: 110.0 mm
  • Approximate weight: 9.558 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 780 A
  • Perm. current rating in air 25°C - trefoil formation: 880 A
  • Maximum operating voltage: 24 kV
  • Rated Voltage Uo/U (Um): 12 / 20 (24) kV
  • Maximum Pulling Tension: 56.7 kN

 

TSLF 36kV 3x1x150A

Nexans ref. 10546319 - Country ref. 1067152

  • Packaging: Drum (500m)
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 86.0 mm
  • Approximate weight: 4.794 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 360 A
  • Perm. current rating in air 25°C - trefoil formation: 370 A
  • Maximum operating voltage: 36 kV
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Maximum Pulling Tension: 13.5 kN

 

TSLF 36kV 3x1x240A

Nexans ref. 10546340 - Country ref. 1067153

  • Packaging: Drum (500m)
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 95.3 mm
  • Approximate weight: 5.97 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 465 A
  • Perm. current rating in air 25°C - trefoil formation: 490 A
  • Maximum operating voltage: 36 kV
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Maximum Pulling Tension: 21.6 kN

 

TSLF 36kV 3x1x400A

Nexans ref. 10546341 - Country ref. 1067154

  • Packaging: Drum (500m)
  • Conductor cross-section: 400 mm²
  • Nominal outer diameter: 108.6 mm
  • Approximate weight: 8.11 kg/m
  • Perm. current rating buried 15°C - trefoil formation: 615 A
  • Perm. current rating in air 25°C - trefoil formation: 680 A
  • Maximum operating voltage: 36 kV
  • Rated Voltage Uo/U (Um): 18 / 30 (36) kV
  • Maximum Pulling Tension: 36 kN

 

Description

Description

Standards

  • International
    HD 620.10K

User benefits:

Diffusion free high voltage cable.

Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.

Screen section: Value given is the physical cross section of the copper wires in the screen of one core.

Usage:

Indoor

Underground

Outdoors

Intended for high voltage energy distribution

Fire propertirs:

Halogen free

Cable marking:

NEXANS NS TSLF 12 kV 1 x mm²/mm² MONTH YEAR

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Number of cores
3

Resources

Resources

Documentation

PEP pdf — 919.4 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close