ENERGYFLEX® 1x10mm² D500

Description

Description

Standards

  • Product
    EN 50618; IEC 62930

Application

Nexans PV H1Z2Z2-K Cable (1.5kV DC)

PV

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Tin Coated Copper Class 5 acc. To EN 60228
Conductor flexibility
Flexible class 5
Insulation
Cross-linked halogen free rubber
Outer sheath
Cross-linked halogen free rubber
Sheath colour
Black (blue or red stripe on request)
Colour
Black
Halogen free
IEC 60754-1; IEC 60754-2
Conductor shape
Circular

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
10 mm²
Nominal outer diameter
7.1 mm
Approximate net weight
122 kg/km
Minimum outer diameter
6.8 mm
Maximum outer diameter
7.8 mm
Conductor diameter
4.0 mm
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
0.8 mm
Outer Diameter
- mm

Electrical characteristics

Electrical characteristics

Maximum permissible nominal current
70 A
Rated Voltage Uo/U (Um)
1.0/1.0 (1.2) kV AC 1.5/1.5 (1.8) kV DC
Max. DC resistance of the conductor at 20°C
1.95 Ohm/km
Maximum DC resistance of the conductor at 90°C
2.330 Ohm/km
Perm current rating in air 30°C
- A
Permissible current rating in air 60°C
98 A
Permissible current rating on a tray 60°C
93 A
Permissible short circuit current conductor 1s
1.3 kA

Mechanical characteristics

Mechanical characteristics

Bending
100 000 cycles in reverse bending
Frequent torsion
100 000 cycles
Mechanical resistance to impacts
Condition AG 2 (medium severity) acc.to HD 60364-5-52
Tensile strength
150 N

Usage characteristics

Usage characteristics

Operating temperature, range
-40 ... 90 °C
Max. conductor temperature in service
120 °C
Packaging
D500
Short-circuit max. conductor temperature
250 °C
Gases corrosivity
IEC 60754-2
Smoke density
IEC 61034-1-2
Ozone resistance
EN 50396:2005
Weather resistance
Excellent
Flame retardant
IEC 60332-1
Corrosive or Polluting Substances
Condition AF 3 (intermittent accidential) acc. to HD 60364-5-52
Length
- m
Minimum Bend Radius - Installed
23.4 mm
Outdoor Use
Condition AN 3 (high solar radiation), permanent according to EN 50565-1:2014
Resistance to vibrations
Condition AH 3 (sever industrial conditions) acc. to HD 60364-5-52
RoHS conform
RoHS 2011/65/EU
Thermal endurance
IEC 60216-1-2
U.V resistance
EN 50289-4-17 method A, for 720h. Nexans prestige test 4000h
Water proof
Passed 100 days 50°C water immersion test of EN 50525-2-21 annex D and E

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close