BFSI 0.6/1kV 4x16/16

Description

Description

Standards

  • International
    IEC 60228; IEC 60331-21 ; IEC 60332-1-2; IEC 60332-3 Cat.C; IEC 60754-1; IEC 60754-2; IEC 61034
  • National
    NEK HD 604-5D

Recommended for indoor and outdoor use in all areas, and in the ground without extra protection, where it is required that the cable shall operate and fully maintain its function in a fire situation. The product is designed and tested to last minimum 90 minutes, and up to a temperature of 1000 deg. Celsius during a fire. Suitable for low voltage systems; 230 V, 400 V and 690 V.

The orange outer sheath will fade to white over time if exposed by sunlight. This fading will not degrade the cable, however UV protection In areas with extra high UV intensity could be considered. 

The copper screen is dimensioned to fulfill the requirements to earth conductor (PE).

Some smaller cross sections are manufactured as EMC types (aluminium tape screen + copper earth conductor, that is possible to separate from outer sheath). Please see product list for details regarding EMC and standard types.

The product is compliant with NEK-HD 604-5D, which specifies particular requirements regarding durability in cold environments and protection against water intruision, suitable for norwegian climate and conditions.

Tested for fire resistance and functional capability for 90 minutes or more.

BFSI is a low smoke, fire resistant and halogen free version of cabletype PFSP 0.6/1 kV.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Bare annealed copper stranded
Conductor shape
Circular
Halogen free
Yes
Insulation
XLPE + Mica tape
Outer sheath
PE
Sheath colour
Orange
Type of conductor
Circular, stranded
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
122.0 kg/100m
Approximate weight
1220 kg/km
Conductor cross-section
16 mm²
Conductor diameter
4.8 mm
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
23.8 mm
Number of cores
4
Number of strands
7
Screen section
16 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Fire load
- MJ/km
Fire resistant
IEC 60331
Fire retardant
IEC 60332-3-24
Length
- m
Max. conductor temperature in service
90 °C
Minimum installation temperature
10 °C
Minimum operating temperature
-40 °C
Packaging
Drum

Resources

Resources

Selling & delivery Information

The cable is marked with LIFEMARK™.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close