TFXP 1kV 4G150A
TFXP 1kV 4G150A
- Nexans ref. : 10022130
- Country ref. : 1017594
- EAN : 7330000055858
Description
Description
Standards
- 
                                            ProductHD 603.5M
- 
                                            TestIEC 60332-1
User benefits:
TFXP has XLPE-insulated aluminium conductors.
The cable is specially devoloped for low temperature conditions.
Installation:
- Underground
- Outdoor
Usage 
- Energy distribution
Marking 
NEXANS GS TFXP n x mm2 1kV YEAR MONTH
Conductor marking/colour code
Black-Brown-Grey-Green/Yellow
Characteristics
Characteristics
Construction characteristics
Construction characteristics
                                                                Conductor material
                                                            
                                                            
                                                                Aluminum 
                                                            
                                                        
                                                                Conductor shape
                                                            
                                                            
                                                                Sector-shaped stranded (SM) 
                                                            
                                                        
                                                                Insulation
                                                            
                                                            
                                                                XLPE (chemical) 
                                                            
                                                        
                                                                With Green/Yellow core
                                                            
                                                            
                                                                Yes 
                                                            
                                                        
                                                                Material of filler / inner sheath
                                                            
                                                            
                                                                PE 
                                                            
                                                        
                                                                Outer sheath
                                                            
                                                            
                                                                PVC 
                                                            
                                                        
                                                                Sheath colour
                                                            
                                                            
                                                                Green 
                                                            
                                                        
                                                                Conductor flexibility
                                                            
                                                            
                                                                Stranded class 2 
                                                            
                                                        Dimensional characteristics
Dimensional characteristics
                                                                Conductor cross-section
                                                            
                                                            
                                                                150 mm²
                                                            
                                                        
                                                                Conductor diameter
                                                            
                                                            
                                                                - mm
                                                            
                                                        
                                                                Sector-shaped heigth
                                                            
                                                            
                                                                15.5 mm
                                                            
                                                        
                                                                Sector-shaped width
                                                            
                                                            
                                                                21 mm
                                                            
                                                        
                                                                Number of cores
                                                            
                                                            
                                                                4 
                                                            
                                                        
                                                                Nominal outer diameter
                                                            
                                                            
                                                                45.0 mm
                                                            
                                                        
                                                                Approximate weight
                                                            
                                                            
                                                                2.38 kg/m
                                                            
                                                        
                                                                Diameter over inner sheath
                                                            
                                                            
                                                                2 mm
                                                            
                                                        
                                                                Nominal insulation thickness
                                                            
                                                            
                                                                1.4 mm
                                                            
                                                        
                                                                Nominal outer sheath thickness
                                                            
                                                            
                                                                1.6 mm
                                                            
                                                        Electrical characteristics
Electrical characteristics
                                                                Permissible current rating in open air
                                                            
                                                            
                                                                320 A
                                                            
                                                        
                                                                Permissible current rating when buried
                                                            
                                                            
                                                                335 A
                                                            
                                                        
                                                                Max. DC resistance of the conductor at 20°C
                                                            
                                                            
                                                                0.206 Ohm/km
                                                            
                                                        
                                                                Inductive reactance at 50Hz
                                                            
                                                            
                                                                0.072 Ohm/km
                                                            
                                                        
                                                                Nominal inductance
                                                            
                                                            
                                                                0.23 mH/km
                                                            
                                                        
                                                                Zero sequence reactance at 50HZ
                                                            
                                                            
                                                                0.31 Ohm/km
                                                            
                                                        
                                                                Zero sequence resistance at 20°C
                                                            
                                                            
                                                                0.824 Ohm/km
                                                            
                                                        
                                                                Capacity of phase cores approx.
                                                            
                                                            
                                                                0.13 µF / km
                                                            
                                                        
                                                                Permissible short circuit current conductor 1s
                                                            
                                                            
                                                                13.5 kA
                                                            
                                                        
                                                                Rated Voltage Uo/U (Um)
                                                            
                                                            
                                                                0.6/ 1 (1.2) kV 
                                                            
                                                        Mechanical characteristics
Mechanical characteristics
                                                                Maximum Pulling Tension
                                                            
                                                            
                                                                18 kN
                                                            
                                                        
                                                                Minimum repeated bending diameter
                                                            
                                                            
                                                                540 mm
                                                            
                                                        Usage characteristics
Usage characteristics
                                                                Packaging
                                                            
                                                            
                                                                NX16 
                                                            
                                                        
                                                                Length
                                                            
                                                            
                                                                500 m
                                                            
                                                        
                                                                Maximum operating temperature
                                                            
                                                            
                                                                90 °C
                                                            
                                                        
                                                                Short-circuit max. conductor temperature
                                                            
                                                            
                                                                250 °C
                                                            
                                                        
                                                                Minimum installation temperature
                                                            
                                                            
                                                                -10 °C
                                                            
                                                        
                                                                Bending factor when laying
                                                            
                                                            
                                                                6 (xD)
                                                            
                                                        
                                                                Flame retardant
                                                            
                                                            
                                                                IEC 60332-1 
                                                            