PFSP 1 kV Aluminium (CPR)

Products

PFSP 1kV 3x25A/10

Nexans ref. 10021739 - Country ref. 1067090

  • Packaging: Drum (999m)
  • Conductor shape: Circular stranded (RM)
  • Nominal outer diameter: 24.1 mm
  • Approximate weight: 62.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 3x50A/16

Nexans ref. 10021740 - Country ref. 1067091

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 27.3 mm
  • Approximate weight: 100.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 3x95A/35

Nexans ref. 10021741 - Country ref. 1067092

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 36.0 mm
  • Approximate weight: 182.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 3x150A/50

Nexans ref. 10021742 - Country ref. 1067093

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 42.1 mm
  • Approximate weight: 252.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 3x240A/70

Nexans ref. 10021743 - Country ref. 1067094

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 51.6 mm
  • Approximate weight: 390.0 kg/100m
  • Length: 400 m

 

PFSP 1kV 4x25A/10

Nexans ref. 10021744 - Country ref. 1067095

  • Packaging: Drum (999m)
  • Conductor shape: Circular stranded (RM)
  • Nominal outer diameter: 26.1 mm
  • Approximate weight: 74.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 4x50A/16

Nexans ref. 10021745 - Country ref. 1067096

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 31.0 mm
  • Approximate weight: 124.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 4x95A/35

Nexans ref. 10021746 - Country ref. 1067097

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 39.7 mm
  • Approximate weight: 225.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 4x150 A/50

Nexans ref. 10021747 - Country ref. 1067098

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 46.1 mm
  • Approximate weight: 312.0 kg/100m
  • Length: 500 m

 

PFSP 1kV 4x240A/70

Nexans ref. 10021748 - Country ref. 1067099

  • Packaging: Drum (999m)
  • Conductor shape: Sector-shaped stranded (SM)
  • Nominal outer diameter: 59.0 mm
  • Approximate weight: 490.0 kg/100m
  • Length: 400 m

 

Description

Description

Standards

  • International
    EN 50265; HD 603.3J; IEC 60332-1

Recommended for use in all room types, and outdoors in-ground without extra protection. Suitable for low voltage systems i.e. 230V, 400V and 690V.

The copper screen is dimensioned to fulfill the requirements for earth conductor (PE) or  combined earth- and neutral conductor (PEN). The screen is made of copper wires with a counter helix to ensure contact between the individual wires. The cable meets the fire classification according to CPR class E.

 

Min. installation temperature without extra precautions: 0°C

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Core identification
Colours
Insulation
PVC
Outer sheath
PVC
Conductor flexibility
Class 2
Lead free
Yes
Sheath colour
Grey

Dimensional characteristics

Dimensional characteristics

Conductor diameter
- mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Bending factor when installed
8 (xD)
Installation type
Outdoor - Direct burial
Max. conductor temperature in service
70 °C

Resources

Resources

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium –

Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground

Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1.5 14.0 0.0 16.5 0.0 19.5 0.0 22.0 0.0 22.0 0.0 22.0 0.0
2.5 18.5 14.5 23.0 17.5 27.0 21.0 27.0 22.0 28.0 0.0 30.0 23.0
4.0 25.0 19.5 30.0 24.0 36.0 28.0 37.0 29.0 38.0 0.0 40.0 31.0
6.0 32.0 25.0 38.0 30.0 46.0 36.0 46.0 36.0 48.0 0.0 51.0 39.0
10.0 43.0 33.0 52.0 41.0 63.0 49.0 60.0 47.0 64.0 0.0 70.0 54.0
16.0 57.0 44.0 69.0 54.0 85.0 66.0 78.0 61.0 83.0 63.0 94.0 73.0
25.0 75.0 58.0 90.0 71.0 112.0 83.0 99.0 77.0 110.0 82.0 119.0 89.0
35.0 92.0 71.0 111.0 86.0 138.0 103.0 119.0 93.0 132.0 98.0 148.0 111.0
50.0 110.0 86.0 133.0 104.0 168.0 125.0 140.0 109.0 156.0 117.0 180.0 135.0
70.0 139.0 108.0 168.0 131.0 213.0 160.0 173.0 135.0 192.0 145.0 232.0 173.0
95.0 167.0 130.0 201.0 157.0 258.0 195.0 204.0 159.0 230.0 173.0 282.0 210.0
120.0 192.0 150.0 232.0 181.0 299.0 226.0 231.0 180.0 261.0 200.0 328.0 244.0
150.0 219.0 172.0 258.0 201.0 344.0 261.0 261.0 204.0 293.0 224.0 379.0 282.0
185.0 248.0 195.0 294.0 230.0 392.0 298.0 292.0 228.0 331.0 255.0 434.0 322.0
240.0 291.0 229.0 344.0 269.0 461.0 352.0 336.0 262.0 382.0 298.0 514.0 380.0
300.0 334.0 263.0 394.0 308.0 530.0 406.0 379.0 296.0 427.0 336.0 593.0 439.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium –

Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground

Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1.5 13.0 0.0 15.0 0.0 17.5 0.0 18.0 0.0 19.0 0.0 18.5 0.0
2.5 17.5 13.5 20.0 15.5 24.0 18.5 24.0 18.5 24.0 0.0 25.0 19.5
4.0 23.0 17.5 27.0 21.0 32.0 25.0 30.0 24.0 33.0 0.0 34.0 26.0
6.0 29.0 23.0 34.0 27.0 41.0 32.0 38.0 30.0 41.0 0.0 43.0 33.0
10.0 39.0 31.0 46.0 36.0 57.0 44.0 50.0 39.0 54.0 0.0 60.0 46.0
16.0 52.0 41.0 62.0 48.0 76.0 59.0 64.0 50.0 70.0 53.0 80.0 61.0
25.0 68.0 53.0 80.0 62.0 96.0 73.0 82.0 64.0 92.0 69.0 101.0 78.0
35.0 83.0 65.0 99.0 77.0 119.0 90.0 98.0 77.0 110.0 83.0 126.0 96.0
50.0 99.0 78.0 118.0 92.0 144.0 110.0 116.0 91.0 130.0 99.0 153.0 117.0
70.0 125.0 98.0 149.0 116.0 184.0 140.0 143.0 112.0 162.0 122.0 196.0 150.0
95.0 150.0 118.0 179.0 139.0 223.0 170.0 169.0 132.0 193.0 148.0 238.0 183.0
120.0 172.0 135.0 206.0 160.0 259.0 197.0 192.0 150.0 220.0 169.0 276.0 212.0
150.0 196.0 155.0 225.0 176.0 299.0 227.0 217.0 169.0 246.0 189.0 319.0 245.0
185.0 223.0 176.0 255.0 199.0 341.0 259.0 243.0 190.0 278.0 214.0 364.0 280.0
240.0 261.0 207.0 297.0 232.0 403.0 305.0 280.0 218.0 320.0 250.0 430.0 330.0
300.0 298.0 237.0 339.0 265.0 464.0 351.0 316.0 247.0 359.0 282.0 497.0 381.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Selling & delivery Information

The cable is marked with LIFEMARK™

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close