MPRXCX® 331 Control 0.6/1 (1.2) kV

Description

Description

Standards

  • International
    IEC 60331-1 or 2; IEC 60092-350; IEC 60092-353; IEC 60092-376; IEC 60228; IEC 60331-2; IEC 60332-1; IEC 60332-3-22; IEC 60754-1; IEC 60754-2; IEC 61034

Applications

MPRXCX®331 armoured fire resistant control cables maintain circuit integrity in case of fire by meeting performances requirements from the IEC 60331 series for 90 minutes. They are used for detection and warning systems where enhanced mechanical protection and electrical screening (EMC) is required. Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal asset protection against all risks of fire.

Design

 

1.   Conductor
      Stranded bare copper
      Class 2 

2.   Insulation 
      Mica + XLPE (cross-linked polyethylene)

      Optional: Special fire resistant HF 90 (halogen-free compound)
       with INFIT TM technology up to 4 mm²


 3.  Inner covering
      (lapped)

4.   Armouring
      Bare copper braid, separator tape (optional)

5.   Outer sheath

      Polyolefin SHF 1 (SHF2 on request)
      Colour: orange

 

Marking
 l NEXANS l MPRXCX 331  "n" x (or G) "s" 150/250 V 90°C IEC 60092-353

IEC 60332-3-22  Cat. A IEC 60331-21/1 ww/yy *CE*

+ metric marking

 

Core Identification

5 and above: all cores white coloured, printed with black numbers
Cables with 3 cores and more also with green-yellow core (has to be stated in order).


 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Halogen free
IEC 60754-1
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Number of cores
-
Conductor cross-section
- mm²
Minimum outer diameter
- mm
Maximum outer diameter
- mm
Approximate weight
- kg/km

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
- A
Rated Voltage Uo/U (Um)
0,6/1 kV
Maximum operating voltage
1.2 kV

Usage characteristics

Usage characteristics

Fire resistant
IEC 60331-21
Flame retardant
IEC 60332-3 Cat. A
Gases corrosivity
IEC 60754-2
Smoke density
IEC 61034
Max. conductor temperature in service
90 °C
Minimum operating temperature
-35 °C
Minimum installation temperature
-10 °C
Electro magnetic interference resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close