Beskrivelse
Standarder
Internasjonal : EN 45545 - HL3; EN 50264-3-1; IEC 60228Beskrivelse
Applications
For use in railway vehicles (trains, locomotives, trolley-busses, etc.), switching stations and control panels.
Installation in cable ducts, tubes and outside. For wiring in switching stations and distribution boards up to 1000 V, this cable is short-circuit and earth fault save.
Current-carrying capacity acc. to EN 50343 as well as VDE 0298 part 4.
Complies with performance requirements acc. to EN 45545-2- HL3.
Design
1. Conductor
Flexible stranded tinned copper, class 5 acc. to IEC 60228
Optional halogen-free separator tape
2. Insulation
Cross-linked compound type El 109 acc. to EN 50264-1
Colour: black or grey
3. Screen
Halogen-free foil, tinned copper wire braid, halogen-free separator
4. Outer sheath
Cross-linked compound type EM 104 acc. to EN 50264-1
Oil, diesel, ozone and UV resistant
Colour: black
Cable marking
Ink marking white:
Flamex EN 50264-3-1 3600V (mm²) MM (N)SHXAFCOE 3.6/6 kV I Nexans I WW-YYYY
Egenskaper
Konstruksjonsegenskaper | |
---|---|
Halogenfri | EN 50267-2-1 & EN 60684-2 |
Farge | Svart |
Bruksegenskaper | |
Driftstemperatur område | -40 .. 90°C |
Røyktetthet | IEC 61034-2 & NFF 16101 |
Korrosive gasser | EN 50267-2-2 |
Irriterende avgasser | EN 50305-9.2 |
Flammehemmende | IEC 60332-1-2 |
Brannbegrensende | EN 60332-3-24 & EN 60332-3-25 |
Min. bøyeradius v/gjentatt bøying eller bearbeiding | 10(xD) |
Min. bøyeradius ferdig installert | 5(xD) |
Motstandsdyktighet i forhold til olje | Ja |
Motstandsdyktig mot Ozon | Ja |
Motstandsdyktighet mot UV | Ja |
Karakteristikk | |
See all products | |
|
Produkter og tjenester
Relevant informasjon
Maks kontinuerlig ledertemperatur
Ledertemperatur ved normal drift |
≤ 90 °C / 250.000 timer |
|
≤ 120 °C / 20.000 timer |
Ledertemperatur ved overbelastning |
≤ 160 °C / 50 timer |
Ledertemperatur ved kortslutning (fortinnet leder) |
≤ 200 °C |
Electrical Properties
Nominal voltage |
Uo/U (Umax) = 3.6/6 (7.2) kV |
Max. operating voltage in DC installations, one-sided earthed |
Vo= 4.0 DC |
Testing AC voltage (5 minutes) |
U = 11 kV |
Coupling resistance 10 kHz – 30 MHz, > 16 mm² |
≤ 50 Ohm/km |
Coupling resistance 10 kHz – 30 MHz, 2.5 mm² - 16 mm² |
≤ 150 Ohm/km |