Description
Halogen free, fire resistant, double insulated cables
Standards
International : HD 604.5D; IEC 60228; IEC 60331-21 ; IEC 60332-3 Cat.C; IEC 60754; IEC 61034-1/2Description
ALSECURE® PLUS BFXI 0,6/1 kV cables are designed to be used in safety systems (emergency lights, warning systems, fire fighting equipments, etc ...) in all premises open to the public (concert hall, theaters, cinemas, department stores, hospitals, schools, etc ...), in high-rises buildings, in tunnels, in industries.
ALSECURE® PLUS cables, with MICA tape technology, are fire resistant and fire retardant, low smoke and halogen free. In the event of fire, emitted gazes are non corrosive and have a very low toxicity.
Installation
- To be installed in accordance with the current regulation.
- For indoor and outdoor use. UV-resistant outer sheath, howevere insulated conductors would need extra protection if exposed to UV light.
- If buried into the ground, extra protection is needed, for example conduit or covering boards
Fire performance
Fire resistant according to: IEC 60331-21
Fire retardant according to : IEC 60332-3C
Characteristics
Construction characteristics | |
---|---|
Halogen free | IEC 60754-1 |
Insulation | Micatape + XLPE |
Outer sheath | Halogen free compound |
Sheath colour | Orange |
With Green/Yellow core | No |
Conductor flexibility | Stranded class 2 |
Conductor material | Copper class 2 |
Dimensional characteristics | |
Nominal outer diameter | 13.7mm |
Approximate weight | 309kg/km |
Number of cores | 2 |
Conductor diameter | 3.0mm |
Conductor cross-section | 6mm² |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Mechanical characteristics | |
Cable flexibility | 12 x D |
Usage characteristics | |
Fire resistant | IEC 60331-21 |
Smoke density | IEC 61034 |
Gases toxicity | Low |
Gases corrosivity | IEC 60754-2 |
Max. conductor temperature in service | 90°C |
Flame retardant | IEC 60332 Part 3 Cat. C |