Description
Standards
International : EN 50265; HD 603.3J; IEC 60332-1Description
Recommended for indoor and outdoor use in all areas, and can be installed directly in the ground without extra protection. PFSP 1kV is suitable for all low voltage systems i.e 230V, 400V and 690V.
The copper screen is dimensioned to fulfill the requirements for earth conductor (PE) or combined earth- and neutral conductor (PEN). The copper screen is made of copper wires with a counter helix to ensure contact between the wires.
If the cable is cut outdoor, any end(s) must be sealed if not connected/terminated. This to prevent water intrusion, and possible corrosion in the future.
Min. installation temperature without extra precautions: 0 °C
Characteristics
Construction characteristics | |
---|---|
Sheath colour | Grey |
Conductor material | Bare annealed copper stranded |
Core identification | Colours |
Insulation | PVC |
Lead free | Yes |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Usage characteristics | |
Bending factor when laying | 8(xD) |
Flame retardant | Yes |
Maximum operating temperature | 70°C |
RoHS compliant | Yes |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Current capacity table PVC insulation multicore single phase
- PVC insulation/two loaded conductors, copper or aluminium –
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
-
- A2 Multi-core cable in conduit in a thermally insulated wall
-
- B2 Multi-core cable in conduit on a wooden wall
-
- C Single-core or multi-core cable on a wooden wall
-
- D1 Single-core or Multi-core cable in ducts in the ground
-
- D2 Single-core or Multi-core cables designed to be buried directly in the ground
-
- E Multi-core cable in free air
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
1.5 | 14 | 17 | 20 | 22 | 22 | 22 |
2.5 | 19 | 23 | 27 | 27 | 28 | 30 |
4 | 25 | 30 | 36 | 37 | 38 | 40 |
6 | 32 | 38 | 46 | 46 | 48 | 51 |
10 | 43 | 52 | 63 | 60 | 64 | 70 |
16 | 57 | 69 | 85 | 78 | 83 | 94 |
25 | 75 | 90 | 112 | 99 | 110 | 119 |
35 | 92 | 111 | 138 | 119 | 132 | 148 |
50 | 110 | 133 | 168 | 140 | 156 | 180 |
70 | 139 | 168 | 213 | 173 | 192 | 232 |
95 | 167 | 201 | 258 | 204 | 230 | 282 |
120 | 192 | 232 | 299 | 231 | 261 | 328 |
150 | 219 | 258 | 344 | 261 | 293 | 379 |
185 | 248 | 294 | 392 | 292 | 331 | 434 |
240 | 291 | 344 | 461 | 336 | 382 | 514 |
Current capacity table PVC insulation multicore three phase
- PVC insulation, three loaded conductors/copper or aluminium –
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
-
- A2 Multi-core cable in conduit in a thermally insulated wall
-
- B2 Multi-core cable in conduit on a wooden wall
-
- C Single-core or multi-core cable on a wooden wall
-
- D1 Single-core or Multi-core cable in ducts in the ground
-
- D2 Single-core or Multi-core cables designed to be buried directly in the ground
-
- E Multi-core cable in free air
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
1.5 | 13 | 15 | 18 | 18 | 19 | 19 |
2.5 | 18 | 20 | 24 | 24 | 24 | 25 |
4 | 23 | 27 | 32 | 30 | 33 | 34 |
6 | 29 | 34 | 41 | 38 | 41 | 43 |
10 | 39 | 46 | 57 | 50 | 54 | 60 |
16 | 52 | 62 | 76 | 64 | 70 | 80 |
25 | 68 | 80 | 96 | 82 | 92 | 101 |
35 | 83 | 99 | 119 | 98 | 110 | 126 |
50 | 99 | 118 | 144 | 116 | 130 | 153 |
70 | 125 | 149 | 184 | 143 | 162 | 196 |
95 | 150 | 179 | 223 | 169 | 193 | 238 |
120 | 172 | 206 | 259 | 192 | 220 | 276 |
150 | 196 | 225 | 299 | 217 | 246 | 319 |
185 | 223 | 255 | 341 | 243 | 278 | 364 |
240 | 261 | 297 | 403 | 280 | 320 | 430 |
Selling information
Declaration of Performance
Declaration of Performance No: 1000321-SEGR
- Certification Date: 26/07/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 3
- Notified body : 0366
- Declared performance: Reaction to fire Eca according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10021706 | 1067048 | PFSP 1kV 2x10/10 |
10021707 | 1067049 | PFSP 1kV 2x16/16 |
10021712 | 1067038 | PFSP 1kV 3x10/10 |
10021713 | 1067039 | PFSP 1kV 3x16/16 |
10021714 | 1067044 | PFSP 1kV 3x25/16 |
10021715 | 1067050 | PFSP 1kV 3x35/16 |
10021716 | 1067051 | PFSP 1kV 3x50/25 |
10021717 | 1067052 | PFSP 1kV 3x70/35 |
10021726 | 1067058 | PFSP 1kV 4x6/6 |
10021727 | 1067045 | PFSP 1kV 4x10/10 |
10021728 | 1067046 | PFSP 1kV 4x16/16 |
10021729 | 1067047 | PFSP 1kV 4x25/16 |