Description
Standards
International : EN 50265; HD 603.3J; IEC 60332-1Description
Industrial cable for use on cable ladders and in ducts and pipes. Also recommended for installation in insulated walls without any extra protection. The cable may also be used in non-explosive areas in mines and tunnels. Recommended used on walls outdoor where the cable is not exposed to mechanical stress. The cable is double insulated and may therefor be installed directly into the ground for underground service. For this application, extra mechanical protection such as protection boards must be used.
Characteristics
Construction characteristics | |
---|---|
Sheath colour | Light grey |
Material of filler / inner sheath | Bedding or tape |
Insulation | PVC |
Lead free | Yes |
Outer sheath | PVC |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Usage characteristics | |
Length | 500m |
Packaging | Drum |
Max. conductor temperature in service | 70°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Current capacity table PVC insulation multicore single phase
- PVC insulation/two loaded conductors, copper or aluminium –
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
-
- A2 Multi-core cable in conduit in a thermally insulated wall
-
- B2 Multi-core cable in conduit on a wooden wall
-
- C Single-core or multi-core cable on a wooden wall
-
- D1 Single-core or Multi-core cable in ducts in the ground
-
- D2 Single-core or Multi-core cables designed to be buried directly in the ground
-
- E Multi-core cable in free air
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
6 | 32 | 38 | 46 | 46 | 48 | 51 |
10 | 43 | 52 | 63 | 60 | 64 | 70 |
16 | 57 | 69 | 85 | 78 | 83 | 94 |
25 | 75 | 90 | 112 | 99 | 110 | 119 |
35 | 92 | 111 | 138 | 119 | 132 | 148 |
50 | 110 | 133 | 168 | 140 | 156 | 180 |
70 | 139 | 168 | 213 | 173 | 192 | 232 |
Current capacity table PVC insulation multicore three phase
- PVC insulation, three loaded conductors/copper or aluminium –
- Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
-
- A2 Multi-core cable in conduit in a thermally insulated wall
-
- B2 Multi-core cable in conduit on a wooden wall
-
- C Single-core or multi-core cable on a wooden wall
-
- D1 Single-core or Multi-core cable in ducts in the ground
-
- D2 Single-core or Multi-core cables designed to be buried directly in the ground
-
- E Multi-core cable in free air
Conductor cross-section |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu |
6 | 29 | 34 | 41 | 38 | 41 | 43 |
10 | 39 | 46 | 57 | 50 | 54 | 60 |
16 | 52 | 62 | 76 | 64 | 70 | 80 |
25 | 68 | 80 | 96 | 82 | 92 | 101 |
35 | 83 | 99 | 119 | 98 | 110 | 126 |
50 | 99 | 118 | 144 | 116 | 130 | 153 |
70 | 125 | 149 | 184 | 143 | 162 | 196 |
Selling information
Declaration of Performance
Declaration of Performance No: 1000058-SEGR
- Certification Date: 20/02/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 3
- Notified body : 0366
- Declared performance: Reaction to fire Eca according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10022218 | 1067620 | PFXP 0.6/1kV 4G10 |
10022219 | 1067621 | PFXP 0.6/1kV 4G16 |
10022220 | 1067622 | PFXP 0.6/1kV 4G25 |
10022221 | 1067623 | PFXP 0.6/1kV 4G35 |
10022222 | 1067624 | PFXP 0.6/1kV 4G50 |
10052360 | 1067626 | PFXP 0.6/1kV 5G10 |
10062684 | 1067627 | PFXP 0.6/1kV 5G16 |