UNI Signal (I) 2x2x0,64

Description

Description

Standards

  • Test
    IEC 60332-1-2

Shielded multi-wire paired cable for instrumentation, control and audio applications.
The cable is made up of individually shielded and twisted pairs of tinned conductors.
The cable is equipped with a separate ground wire for good shielding properties.
It has a gray sheath in PVC with an outer diameter of 6.4 mm

Impedance in range 10 - 100 MHz: 75 Ohm
The cable has CPR class Eca

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Stranded tinned copper
Drain wire
Stranded tinned copper
Individual screen
Aluminium / Polyester tape
Insulation
Polyethylene
Insulation colour
Black and red, Green and white
Outer sheath
PVC Flexible
Screen
No
Sheath colour
Grey

Dimensional characteristics

Dimensional characteristics

Approximate weight
61 kg/km
Number of pairs
2
Conductor cross-section
0.64 mm²
Conductor diameter
0.9 mm
Nominal outer diameter
6.4 mm
Number of triples
-

Electrical characteristics

Electrical characteristics

Characteristic impedance
75 Ohm
Conductor electrical resistance
36.7 Ohm/km
Test voltage
1200 V

Usage characteristics

Usage characteristics

Bending factor when laying
15 (xD)
RoHS compliant
Yes
U.V resistance
Yes

Resources

Resources

Declaration of Performance

  • Declaration of Performance n° : 1000854-NOLA
  • Certification Date : 6/11/25
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1783
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close